Thermocouple Cable - PFA Insulated Twisted Pair with Screen
Thermocouple Cables - Single Pair
|
||||||||
PFA Twisted Pair with Screen One pair of solid conductors. Cores PFA insulated. Pair twisted, screened with Mylar aluminium tape and silver plated copper drain wire. PFA sheathed overall. |
PFA Twisted Pair with Screen One pair of stranded conductors Cores PFA insulated. Pair twisted, screened with Mylar aluminium tape and silver plated copper drain wire. PFA sheathed overall. |
|||||||
Stock Number | B70 | B75 | B80 | B85 | ||||
Conductor Style | Solid | Stranded | ||||||
No. of Strands / Strand Diameter (mm) | 1/0.8 | 1/1.29 | 7/0.2 | 13/0.2 | ||||
Total Area (mm2) | 0.5 | 1.3 | 0.22 | 0.44 | ||||
Total AWG (S = Stranded) | 20 | 16 | 24S | 21S | ||||
Insulation | PFA | PFA | ||||||
Number of Pairs | 1 | 1 | ||||||
Laid Flat or Twisted | Twisted | Twisted | ||||||
Screen | Yes | Yes | ||||||
Insulation | PFA | PFA | ||||||
Insulation Rating (ºC) |
Continuous | -75 to +250 | -75 to +250 | |||||
Short Term | +300 | +300 | ||||||
Colour Coding | Yes | Yes | ||||||
Physical Properties |
Abrasion Resistance | Good | Good | |||||
Moisture Resistance | Very Good | Very Good | ||||||
Typical Weight (Kg/100m) excl reel |
3 | 4 | 3 | 3 | ||||
Diameter under Armour (mm) | — | — | ||||||
Diameter over Armour (mm) | — | — | ||||||
Overall Diameter | 4 | 6 | 3 | 4 | ||||
Popular Order Codes | B70KX, B70TX, B70JX, B70NX, B70RCA B75KX, B75TX, B75JX, B75RCA |
B80KX, B80TX, B80JX, B80NX, B80EX, B80RCA B85KX, B85TX, B85JX, B85RCA |
||||||
Notes All dimensions are approximate |
Round section (pair lay visible through sheath). Rejects electromagnetic interference. Gas, steam and water tight insulation. | Round section (pair lay visible
through sheath). Rejects
electromagnetic interference.
Gas, steam and water tight insulation. |